The F141 incorporates two (2) completely separated temperature indicators in one enclosure. There is no relationship between the inputs, even different measuring units can be used. The measuring unit is displayed together with the input channel information A or B. The F141 can be set to show the selected information manually or with an automatic toggle function.
-
The F073 is a versatile level indicator with continuous level monitoring feature. It offers the ability to set one low level and one high level alarm value. If desired, an ignore function can be set up to allow for an incorrect level for a certain period of time. The configuration of the Span, off-set and number of decimals is done through software functions, without any sensitive DIP-switches or trimmers. The display shows the actual level, height or percentage, alarm values, alarm messages and status. On-screen engineering units are easily configured from a comprehensive selection.
-
The F010 is a local weather-proof indicator with large 26mm (1”) high digits which displays the actual flow rate. The measuring and time unit to be displayed below the flow rate are simply selected through an alphanumeric configuration menu. The configuration of K-factors or Span and number of decimals is done through software functions without any sensitive DIP-switches or trimmers.
-
The F490 is a versatile, loop powered Multi Purpose Indicator which displays the actual process value, range and loop current. Besides the focus on level, temperature and pressure applications, the F490 can also work with other measuring units, such as %, mA, RPM and more. Therefore, the F490 is a versatile indicator that suits many applications. At the F490, the input circuit is separated from the backlight circuit. It is designed in such way that it does not influence the intrinsically safe circuit to which it is connected. The F490 accepts 4 - 20mA input signals from a wide range of process instruments, including flow (linear or square root), level, pressure and temperature transmitters. All these process parameters can be displayed in their own engineering units. Thanks to its ruggedness, the F490 withstands extreme weather conditions such as rain, snow, sun, sandy deserts, salty atmospheres and temperatures between -40°C/-40°F and +80°C/+178°F without the need for expensive protective cabinets. Moreover, all products in the F-series are robust by design: even a truck can stand on them.
Hazardous area information
The F490 is certified according ATEX, IECEx and CSA for use in Intrinsically Safe applications with an ambient temperature of -40°C to +70°C (-40°F to +158°F). ATEX markings: Gas: II 1 G Ex ia IIC T4 Ga Dust: II 1 D Ex ia IIIC T100°C Da IECEx markings: Gas: Ex ia IIC T4 Ga Dust: Ex ia IIIC T100°C Da CSA c-us markings: IS Class I/II/III, Division 1, Groups A to G. Ex ia IIC / Class 1 Zone 0 AEx ia IIC T4. -
The E018 is one of the top models in our range of explosion proof flow computers. In addition to the average K-Factor, 16 linearization points can be entered. The unit will interpolate between these points greatly enhancing accuracy in any flow range. Moreover, a continuous flow rate monitoring feature is available with high and low flow rate alarm values and four alarm outputs.
-
The Pepperl+Fuchs Enviro-Line purging units is an enclosure pressurization system for non hazardous areas that operates on a supply of compressed instrument air or inert gas. It regulates and monitors the pressure within the sealed enclosure at a constant pressure in order to prevent the accumulation of damaging and caustic gases and dusts.
The elimination of these gases and dusts extends the life of expensive electrical equipment and instrumentation placed within the Enviro-Line purging unit.Due to higher pressures inside the electrical enclosure, corrosive environments remain outside. The system maintains a constant 0.5" water pressure inside the enclosure for protection against gas and/or dust.- Environmental purge for nonhazardous areas
- Built in ISO 9001 registered manufacturing facilities
- Complete package for enclosures up to 7.2 m3 (250 ft3)
-
ECT DIN-style signal isolators, converters, repeaters, boosters and splitters feature solid metal housings that stand up to the continuous, daily rigors of process control and factory automation applications. Rugged and reliable, the ECT is available in 2-wire (loop) and 4-wire (line/mains) powered models. The complete family delivers economical solutions for an expansive range of signal interface applications. Download Data Sheet
-
The ECA DIN-style Alarm features a solid metal housing that stands up to the continual rigors of process control and factory automation applications. Rugged and reliable, the 4-wire (line-powered) ECA is the low-cost solution when alarm trip outputs are needed to indicate high or low process conditions. Available models accept current and voltage input from field transmitters, transducers, and other process instruments. When the input falls outside of a pre-set limit (user configurable), the ECA provides contact closure outputs ideal for indicating a high and/or low condition via a bell, buzzer, light or other annunciating device.
-
The E115 has been developed for applications where the direction of flow is an issue. Applications can be found by loading and unloading of ships where one bi-directional flowmeter is used. Another application is the correction of back-flow due to shocks in a pipeline caused by piston pumps or valve behavior. It is required to offer two pulse signals from the flowmeter which are 90° or 270° degrees out of phase.The E-series distinguishes itself by its quality and functionality driven European design and manufacturing. It is more than fulfilling the rules for explosion proof design, it is about safety during the daily operation. Often, the environment is much tougher than the explosion proof requirements demand. Thus dangerous conditions may be experienced due to a broken enclosure or a poorly made flame path. Ruggedness and reliability is where Fluidwell stands for and it is now available in a comprehensive well designed and purpose driven explosion proof flow rate indicator / totalizer.
Features:
- Explosion proof according ATEX, IECEx, FM and CSA C-US.
- Aluminum or high grade stainless steel Ex d enclosure.
- Easy installation with the spacious chamber and plug & play connectors.
- Cost saving with an easy to install, 1” NPT thread for direct flowmeter mounting.
- Detects flow direction with quadrature signal inputs.
- Key information at a glance as the display shows forward & reverse flow rate, forward & reverse total, accumulated total count up and count down ref. flow direction, measuring units and a flow rate indicating speedometer.
- Easy K-factor and engineering unit configuration for volumetric or mass. Learn more with this interactive tutorial.
- 7 digit flow rate / total and 11 digit accumulated total.
- Bright LED backlight.
- Easy configurable via PC with free downloadable remote configuration tool and special communication cable (ACE01/02/06/07).
- Auto backup of settings and running totals.
- Ambient temperature: -40°C to +70°C (-40°F to 158°F).
- Various accessories are available for this product.
Hazardous area information:
- The E-Series are ATEX, IECEx, FM and CSA C-US certified for an ambient temperature range of -40°C to +70°C (-40°F to +158°F).